Specifications
118
APPENDIX A — CCN POINTS (cont)
CIRCUITA — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display CMPA1 Compressor A1 NO ON/OFF — On/Off OUTPUTS A1
Status Display CSB_A1 Compressor A1 Feedback NO ON/OFF — On/Off INPUTS CS.A1
Status Display CMPA1_TG Compressor A1 Timeguard NO XXXX SEC 0-1000 INPUTS TG.A1
Status Display CMPA2 Compressor A2 NO ON/OFF — On/Off OUTPUTS A2
Status Display CSB_A2 Compressor A2 Feedback NO ON/OFF — On/Off INPUTS CS.A2
Status Display CMPA2_TG Compressor A2 Timeguard NO XXXX SEC 0-1000 INPUTS TG.A1
Status Display MLV Minimum Load Valve NO ON/OFF — On/Off CONFIGURATION S.MLV
Status Display SP_A Cir A Suction Pressure NO XXX.X PSIG 0 TO 450 PRESSURES SSP.A
Status Display SSTA Cir A Sat Suction Temp YES XXX.X F -40 TO 160 TEMPERATURES SST.A
Status Display DP_A Cir A Discharge Pressure NO XXX.X PSIG 0 TO 450 PRESSURES SCP.A
Status Display SCTA Cir A Sat Condensing Tmp YES XXX.X F -40 TO 160 TEMPERATURES SCT.A
CIRCUITB — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display CMPB1 Compressor B1 NO ON/OFF — On/Off OUTPUTS B1
Status Display CSB_B1 Compressor B1 Feedback NO ON/OFF — On/Off INPUTS CS.B1
Status Display CMPB1_TG Compressor A1 Timeguard NO XXXX SEC 0-1000 INPUTS TG.B1
Status Display CMPB2 Compressor B2 NO ON/OFF — On/Off OUTPUTS B2
Status Display CSB_B2 Compressor B2 Feedback NO ON/OFF — On/Off INPUTS CS.B2
Status Display CMPB2_TG Compressor B2 Timeguard NO XXXX SEC 0-1000 INPUTS TG.B2
Status Display SP_B Cir B Suction Pressure NO XXX.X PSIG 0 TO 450 PRESSURES SSP.B
Status Display SSTB Cir B Sat Suction Temp YES XXX.X F -40 TO 160 TEMPERATURES SST.B
Status Display DP_B Cir B Discharge Pressure NO XXX.X PSIG 0 TO 450 PRESSURES SCP.B
Status Display SCTB Cir B Sat Condensing Tmp YES XXX.X F -40 TO 160 TEMPERATURES SCT.B
ECONWORK — POINTS
DESCRIPTION
CCN POINT
NAME
EXPANDED NAME
READ/WRITE
PROPERTIES
DISPLAY UNITS DISPLAY RANGE
SCROLLING
MARQUEE TABLE
SHORT
DISPLAY NAME
Status Display ECONENBL Remote Economizer Enable YES ON/OFF — On/Off INPUTS E.ENA
Status Display ECOORIDE Econo Position Override YES ON/OFF — On/Off INPUTS E.OVR
Status Display ECACTIVE Economizer Active ? NO YES/NO — Yes/No — —
Status Display MIN_POS Econo Current Min. Pos. NO XXX % 0-100% INPUTS E.MPO
Status Display OAE Outdoor Air Enthalpy NO XX.XX BTU/LB 18-28 BTU/LB INPUTS OA.E
Status Display RAE Return Air Enthalpy NO XX.XX BTU/LB 18-28 BTU/LB INPUTS RA.E
Status Display OAEC_SEL A,B,C,D Curve Select YES 1,2,3,4,5 —
A=1, B=2, C=3, D=4,
CUSTOM=5
CONFIGURATION OA.EC
Status Display OAEN_CFG Outdr.Enth Compare Value YES XX.XX BTU/LB 0-50 BTU/LB CONFIGURATION OA.EN
Status Display ECONCPNT Economizer Control Point YES XXX.X F control temperature for economizer — —
Status Display EDT Evaporator Discharge Tmp NO XXX.X F TEMPERATURES EDT
Status Display SFAN Supply Fan State YES ON/OFF — On/Off OUTPUTS S.FAN
Status Display ECONOCMD Econo Damper Command Pos YES XXX % 0-100% OUTPUTS E.PWR
Status Display ECONOPOS Econo Damper Current Pos NO XXX % 0-100% OUTPUTS EC.AP
Status Display OAT Outside Air Temperature YES XXX.X F -40 TO 240.1 TEMPERATURES OAT
Status Display RETURN_T Controlling Return Temp YES XXX.X F 40.1 TO 240.1 — —
Status Display SPACE_T Controlling Space Temp YES XXX.X F 40 t0 90 — —
Status Display SENSUSED SPT/RAT sensors used NO YES/NO — Yes/No — —
Status Display ECONHELD Econ recovery hold off? NO YES/NO — Yes/No — —
Status Display RAT_LOW Return Temp too low ? NO YES/NO — Yes/No — —
Status Display OAT_LOCK High OAT Lockout Temp YES XXX.X — 55 TO 120 F CONFIGURATION OAT.L
Status Display RATSENS Return Air Temp Sensor YES ENABLE/DISABLE — Enable/Disable — —
Status Display ECONBAND Economizer Temp Deadband YES XXX.X F 0.5 TO 5.0 CONFIGURATION EC.CB
Status Display ECONRATE Economizer Run Time Rate YES XXX.X — 0 TO 120 SEC — —
Status Display ECON_SEL Econ ChangeOver Select YES 1,2,3,4,5 —
1=Drybulb,2=Diff Drybulb,
3=Enthaply Curve, 4= Diff Enthalpy
CONFIGURATION E.CGO
Status Display ECONOMIN Economizer Min.Position YES XXX % 0-100% CONFIGURATION MIN.P
Status Display IAQMINP IAQ Demand Vent Min.Pos. YES XXX % 0-100% CONFIGURATION AQ.MP