Specifications
6 CVHE-SVN03D-EN
Customer Supplied
Remote Starter
Table 2. CVHE, CVHF, and CVHG standard customer supplied remote field wiring requirements
Power supply wiring (to Starter Panel) Starter Panel Terminals
Starter by others Power wiring:
3-Phase Power Supply
Starter and Motor Junction Box
Interconnection (Remote starter only)
See “Starter by others”
schematic
All wiring to be in
accordance with National
Electrical Code and any local
codes.
Starter provided by others:
Starter to UCP 120VAC control wiring Starter to UCP 120VAC
control wiring
Unit Control Panel
Terminations
120VAC Power Supply See “Starter by others”
schematic
5X1-1, 5X1-2, 5X1-20
(Ground)
1X1-1, 1X1-12, 1X1-18 #8 gauge minimum 40 amps
circuit
Power from UCP 1Q1 5X1-3 1X1-3, 1A23-J6-3 14 ga.
Interlock Relay signal 5X1-4 1A23-J10-1 14 ga.
Start contactor signal 5X1-5 1A23-J8-1 14 ga.
Oil Pump Interlock 5X1-7, 5X1-8 1A7-J2-4, 1A7-J2-2 14 ga.
Run Contactor signal 5X1-10 1A23-J6-12 14 ga.
Transition Complete 5X1-14 1A23-J12-2 14 ga.
Low Voltage Circuits (less than 30VAC) Starter Panel
Terminals
Unit Control Panel
Terminations
Standard Circuits
Current Transformers* (see table next page) 5CT4- wht, blk
5CT5- wht, blk
5CT6- wht, blk
1A23-J7-1,2
1A23-J7-3,4,
1A23-J7-5,6,
Note: Phasing must be
maintained
Potential Transformers 5T17-236,237
5T18-238,239
5T19-240,241
1A23 –J5-1,2,
1A23 –J5-3,4,
1A23 –J5-5,6
Note: Phasing must be
maintained
Starter Supplied by Others -Standard Field Power wiring:
Note: All wiring to be in accordance with National Electrical Code and any local codes.
Reference Field Connection Customer Supplied Starter diagram 2309-4936 in this manual
Reference “Starter by Others” Specification available from your local Trane sales office.