Specifications
Field Control Panel Signal Wiring
20 CVHE-SVN03D-EN
Control Panel Internally
mounted devices
For visual identification Internal
Control Panel mounted devices are
identified by their respective
schematic designation number.
Control panel items are marked on
the inner back panel in the control
panel. Figure 7 illustrated below,
identifies these devices. The Control
Panel Devices table corresponds to
the same device designators (see
right hand column). Optional
controls are present when a specific
optional controls package is
specified, as listed in the second
column.
Figure 7. Standard Enclosure
Note: UCP control wiring (120 VAC) must not be routed with low voltage circuits (less than 30 VAC). Conduit
access holes are furnished in the top of the unit control panel. Use the left holes for low voltage wiring, and
use center and right hand holes for control (120 VAC) wiring.
Note: The wire is retained in the clamp by the force of the spring which pushes the wire against the
connecting bar. Use care to ensure full insertion of screwdriver into terminal block wire release mechanism.
Proper tool engagement is required to release the tension for wire insertion.
L
ow voltage entrances
(
less than 30 VAC)
Control wiring (120 VAC)
Optional controls packages are;
OPST Operating Status, GBAS
Generic Building Systems, EXOP
Extended operation, CDRP
Condenser Pressure, TRMM Tracer
communications, WPSR Water Flow
Pressure sensing, FRCL Free
Cooling, HGBP Hot Gas Bypass, and
EPRO Enhanced Protection.
Figure 20 illustrates the Control
Panel Components Layout.
Modules 1A1, 1A3, 1A4, 1A5, 1A6,
1A7, and 1A13 are standard and
present in all configurations. Other
Modules vary depending on
machine optional devices.