REX Meter
Technical Manual 6 Installation and Removal
Initial Setup After installing and powering the REX meter, verify the following:
■ If there is a load, the K
h
pulse indicator on the LCD is flashing, and the
arrows indicate the correct energy flow direction.
■ Required meter seals are in place.
■ Any information (such as location of the meter) has been recorded.
If the meter is not working correctly after it has been installed, then check for
improper installation or wiring. If the installation and wiring are correct, then
check these other areas:
■ the meter installation matches the meter nameplate
■ the correct type of REX meter is installed in the existing service
■ no evidence of mechanical or electrical damage to either the meter or
the installation location
■ the service voltage falls within the operating range as indicated on the
nameplate
■ the seals are not broken
A broken seal could be an indication of tampering with the REX meter
installation.