The load profiling interval is specified in minutes and must be 15, 30, or 60
minutes. The load profiling interval length can be different from the demand
interval length.
Note: If the metered quantity is kWh net, load profiling stores the
number of kWh delivered pulses.
K
h
pulse divisor. A pulse divisor is used to scale down the number of K
h
pulses recorded in each load profiling interval. This allows recording of data that
may exceed the maximum number of pulses that can be stored in each load
profiling interval (each interval can store 4095 pulses before overflowing).
The standard value of K
h
for all REX meters is 1.0. If the divisor is set to 10, then
each load profiling pulse count represents 10 Wh.
Physical Description The physical components of the REX meter consist of the following:
meter cover
nameplate
inner housing
main circuit board
circuit board support frame
meter base
See Figure 2-4 for an illustration of the REX meter physical components.
Interval length
1
1
An A3 ALPHA meter/collector is required to read the REX meter and accumulate larger
load profiling records.
Maximum storage capacity
Release 1.0 & 2.0 Release 3.0 and higher
15 minutes 26 hours 120 hours
30 minutes 52 hours 240 hours
60 minutes 104 hours 480 hours