General
This leaflet contains installation instructions for the REX single phase electronic watthour meter with the following form
factors:
■ self-contained: Forms 1S and 2S
■ transformer-rated: Forms 3S and 4S
All meters are calibrated and sealed before shipment. For proper installation, accuracy, and maximum life of the meters,
use the following procedures.
Installing the REX Meter
1 Make sure the meter to be installed matches service type (that is, form), current class, capacity required, and
service socket.
2 Check the socket and verify that the wiring is correct. See Figure 1 for self-contained meters and Figure 2 for
transformer-rated meters.
3 Make sure that the voltage disconnect or test link on the back of the meter is closed, if installed.
4 Line up the meter blades to the socket jaws and rock the meter into place. Make sure that the meter is in the
upright position.
5 Make sure the LCD turns on and the energy use indicator arrow flashes if load is present.
If load is applied, check that the pulse arrows on the LCD are blinking. The LCD has 2 pulse arrows. The arrow
pointing to the left indicates energy received; the arrow pointing to the right indicates energy delivered. For
more information, see the technical manual for your meter.
6 Apply all seals and record any necessary information.
WARNING
!
Use authorized utility procedures to install and service metering equipment. Dangerous voltages are present. Equipment
damage, personal injury, or death can result if safety precautions are not followed.
FCC and Industry Canada Compliance
Compliance Statement (Part 15.19): The REX meter complies with Part 15 of the FCC Rules and with RSS-210 of Industry
Canada. Operation is subject to the following two conditions: 1) This device may not cause harmful interference, and 2) This device must
accept any interference received, including interference that may cause undesired operation.
Warning (Part 15.21): Changes or modifications not expressly approved by Elster Electricity, LLC could void the user’s authority to
operate the equipment.
RF Radiation Safety Guidelines per Part 2 of FCC Rules and Regulations: The meter should be installed in a location where
there will be a separation greater than 20 cm from locations occupied by humans.
User Information (Part 15.105): The REX meter has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, the
user is encouraged to try to correct the interference by one or more of the following measures:
■ Reorient or relocate the receiving antenna.
■ Move the receiving equipment farther away from the REX meter.
■ Consult the dealer or an experienced radio/TV technician for help.
Industry Canada Statement: The term “IC” before the certification/registration number only signifies that the Industry Canada
technical specifications were met.