User's Manual
A3 ALPHA Meter/Collector PG42-1005A
8 July 2003
If the A3 ALPHA meter/collector must be taken out of service (because of an
error condition, the telephone modem fails, etc.), the A3 ALPHA meter/collector
can be replaced with another A3 ALPHA meter/collector.
Since the REX meters within the network register with a meter/collector, a
change out procedure needs to be performed to make certain that the REX
meters will communicate with the new A3 ALPHA meter/collector. Follow these
steps to change out an old meter/collector with a new meter/collector:
1 Before beginning the change out procedure, verify that the new A3 ALPHA
meter/collector is properly configured (see Metercat Program Development
Guide for specific details).
2 Using Metercat software, perform a billing or diagnostic read on the old A3
ALPHA meter/collector. Be certain to include storage mode (either append or
replace) and all of the internal LAN controller data in the read.
3 Make a note of the old A3 ALPHA meter/collector LAN ID obtained from the
billing or diagnostic read performed in step 2.
4 Remove the old A3 ALPHA meter/collector from service. (See A3 ALPHA
Meter Technical Manual for specific details).
5 Install the new A3 ALPHA meter/collector. Be sure to follow the installation
instructions that are provided with the A3 ALPHA meter/collector to correctly
install the meter/collector.
6 Using Metercat software, perform the "Change Out LAN Collector" function.
(See Metercat user Guide for specific details). The old A3 ALPHA meter/
collector LAN ID obtained in step 3 will be needed to complete the change
out function.
After the change out command is performed, the REX meters will re-register with
the new A3 ALPHA meter/collector.
Changing an A3 ALPHA
Meter with ILC1 Option
Board
Use authorized utility procedures to remove metering equipment. Dangerous
voltages are present. Equipment damage, personal injury, or death can result if
safety procedures are not followed.
WARNING
!
The A3 ALPHA meter display can be divided into different regions as shown in
Figure 3. See Chapter 3, "Operating Instructions," in the A3 ALPHA meter
technical manual (TM42-2190) for more detailed descriptions of the LCD and its
display regions.
Display List Items
ARh
CUM
KW
RATE
TOTAL
RESETS
CONT
MAX
ABCD
PREV SEAS
TEST
ALT
EOI
Quantity identifier
Operating mode
indicator
Display
quantity
Potential
indicators
End of interval
indicator
Real energy
indicators
Alternate
energy
indicators
Power/energy
units identifier
Display identifiers
Figure 3. A3 ALPHA meter LCD