MEASUREMENT RANGE, RESOLUTION, ACCURACY:
1
Depending on the Clamp Accuracy
POWER & ENERGY MEASUREMENT RANGE RESOLUTION ACCURACY
Active Power Depends on Clamp & PT
Configuration
10mW ±0.2%
1
Reactive Power Depends on Clamp & PT
Configuration
10mVAR ±2%
1
Apparent Power Depends on Clamp & PT
Configuration
10mVA ±0.2%
1
Active Energy Depends on Clamp & PT
Configuration
10mWh ±0.2%
1
Reactive Energy Depends on Clamp & PT
Configuration
10mVArh
%
1
Apparent Energy Depends on Clamp & PT
Configuration
10mVAh ±0.2%
1
True Power Factor ±1 (CAP\IND) 10µ ±0.2%
1
Displacement Power Factor ±1 (CAP\IND) 10µ ±0.2%
1
FLICKERING MEASUREMENT RANGE RESOLUTION ACCURACY
P
SST
, P
ST
10 Minutes, S
PLT
, P
LT
2
Hours, L
PLT
0 to 20 0.01 ±5%
PST
INST
0 to 20 0.01 ±8%
UNBALANCE MEASUREMENT RANGE RESOLUTION ACCURACY
Volts (Negative & Zero Seq.)
Ratio
0 to 100% 0.1% 0.15%
Current (Negative & Zero Seq.)
Ratio
0 to 100% 0.1% 0.5%
1
TRANSIENT CAPTURE ACCURACY
Minimum Detection Duration 39 μs (G3500)
19.5 μs (G4500)