MEASUREMENT RANGE, RESOLUTION, ACCURACY:
1
For Nominal Voltage 80 to 690V
2
Depending on the Clamp Accuracy
VOLT/AMPS/HERTZ MEASUREMENT RANGE RESOLUTION ACCURACY
V
RMS
(AC & DC) 0 to 900V 0.01V ±0.1% of Nominal Voltage
1
A
RMS
With SOA-9045-3001 90A to 15kA 0.1mA ±0.5% ±0.5A of Nominal
Current
2
With SOA-9091-3000 9 to 1.5kA 0.1mA ±0.8% ±0.1Aof Nominal
Current
2
With SOA-0010-0500 0.02 to 6A 0.1mA ±0.15% ±0.5mAof Nominal
Current
2
V
Pk
8KV 10mV ±0.1% from Reading
Voltage Crest Factor 1< 0.01 Better than 0.5%
Current Crest Factor 1< 0.01 Better than 0.5%
Hz @ 50Hz Nominal 42.5 to 62Hz 10mHz ±5mHz
Hz @ 60Hz Nominal 51 to 69Hz 10mHz ±5mHz
K-Factor 0< 0.01 ±0.25%
DIPS, SWELLS & INTERRUPTIONS MEASUREMENT RANGE RESOLUTION ACCURACY
V
RMS
½ (AC & DC) 0 to 900V 0.01V ±0.2% of Nominal Voltage
Duration HHH,MM,SS,MMM Half Cycle One Cycle
Threshold Levels Programmable Thresholds & Hysteresis in Percentage of Nominal Voltage
Event Detection Based Upon ½ Cycle RMS Voltages
Captures Dips, Swells, Interruptions & Rapid Voltage Changes
VOLTAGE HARMONICS MEASUREMENT RANGE RESOLUTION ACCURACY
Harmonic Order 1 to 50 Grouping: Harmonic Subgroups According to IEC61000-4-7
Inter-Harmonic Order 1 to 50 Grouping: Inter-Harmonic Subgroups According to IEC61000-4-7
THD
(n=50)
0 to 100% 0.01% ±0.25%
THD Even 0 to 100% 0. 01% ±0.25%
THD Odd 0 to 100% 0.01% ±0.25%
Hz (Spectrum) 0 to 3174Hz fSys 10/12 ±5%
Phase Angle -180 to +180º 0.01º ±0.01º