Verify Power Readings
Although Power Configurations is comprehensively dealt with in the Power Section,
this section is necessary to verify that all the Active Power readings reflect
Positive Values. Corrections can be made by toggling the polarity in the Current
Configurations.
For a full description on all the configurations, definitions & subsequent parameter
calculations see Power.
Access your Portable BLACKBOX Unit via the Web Interface Open
Monitoring Power:
Verify that the Active Power readings reflect Positive Values:
Should any of the Phase Integers display a negative value (as per the
highlighted section above) you will need to Reverse the Polarity for the
Phase in the Current Configurations. Alternatively you may also physically
reverse the current clamp at the power source, by changing the direction.
Generators commonly display a negative Active Power value.