The LED light will illuminate confirming a solid connection:
S
PECIFICATION
G4500
G3500
Number of Inputs 4 (3 Phases & Neutral) +
DC/Ground
4 (3 Phases & Neutral)
Maximum Peak
Measurement
I1 to I4: 10 V
Pk
I5: 3 V
Pk
From Clamp
I1 to I4: 10 V
Pk
From Clamp
Type Clamp On Current Transformer
With mV Output
Clamp On Current Transformer
With mV Output
Range I1 to I4: 0 to 10 V
Pk
I5: 0 to 3 V
Pk
From Clamp
I1 to I4: 0 to 10 V
Pk
From Clamp
Burden 0.05VA (Typical) @ 5 IRMS 0.05VA (Typical) @ 5 IRMS
Bandwidth 25kHz (Typical) @ 5 IRMS 12.5kHz
PLUG IN THE G4500'S VDC PROBES:
The G4500 facilitates Auxiliary DC(+) & DC(-) voltage & current inputs & provides an
independent input to the main AC/DC channel DC voltage readings. The measurement
range ranges from -1000VDC to +1000VDC at a rate of once every second. This is mainly
suitable for a voltage converter DC link side reading while the main voltage channels are on
the grid side.
Plug in the DC Probes into the applicable sockets located on the Rear Panel - Red(+)
& Black(-):
Connect the measurement end to the measured power source
No configuration is necessary for the automatically recognized DC V/I Probes, you
may however choose to Enable / Disable the recording at your own choosing. See
Capture DC.