The Activation area is used to configure the rules that will be applied to
cause real-time activation of the condition (change from 0 -> 1). For ex-
ample, if you set the following: Voltage RMS 1 (X = V1), Compare to is
set to the configured Nominal voltage (say, V = 230V), Deviation is set
10 (D = 10%) and Operation is set 100*(|X-V|/V) >= D, the condition
will be activated when the RMS voltage of channel 1 goes 10% above or
10% below nominal voltage.
The Deactivation area is used to configure the rules that will be applied
to cause real-time de-activation of the condition (change from 1 -> 0).
For example, if you set the following: Voltage RMS 1 (X = V1), Com-
pare to is set to the configured Nominal voltage (say, V = 230V), Devia-
tion is set 10 (D = 10%) and Operation is set 100*(|X-V|/V) < D, the
condition will be de-activated when the RMS voltage of channel 1 goes
below 10% deviation from nominal.
The Compare to list is used to select the type of reference value ("V")
to compare to the X parameter value.
The Parameter is for setting reference to system parameter such as
nominal voltage value.
User Value enables the user to edit his own reference value.
Interval average enables user to compare X to its averaged value over a
defined time interval.
Value ∆ enables dX/dt (time deviation) operation, which means X is
compared to its previous sample value. For instance, if the selected X
parameter is V1 RMS (from group 10[ms] Fast RMS than V = X[-1]
(meaning, previous 10ms RMS value).
Deviation defines the Deviation ("D") value used in the operation for-
mula. Notice that some operations do not contain deviation; in such
cases the deviation configuration is not in use.
Operation defines the rule or mathematical operation to apply for Acti-
vation or Deactivation of condition.
Multiple Type Condition