Specifications

G4500 BLACKBOX PORTABLE OPERATIONAL MANUAL
64
Website | Elspec
The Compliance Info Page
This page contains detailed compliance information.
By clicking on the parameter's text, you get the following detailed informa-
tion:
Status/Partial contains two status indicators. The upper indicator refers to the entire ob-
servation window’s PASS/FAIL result (same status as presented in the Summary page),
while the lower indicator is a PASS/FAIL indicator of the most recent period. This re-
cent indicator is served as real-time indicator and typically reflects only minutes to a few
hours of history (this is dependent on the specific PQ parameter measurement' intervals
and method).
Observation indicates whether the observation window of the PQ parameter is com-
plete.