Uncertainty
Measuring Range
Frequency
±10 mHz
42.5 Hz – 69 Hz
Magnitude of Supply Voltage
±0.1% of Udin
10% – 150% of
Udin
Under-Deviation and Over-
Deviation
±0.1% of Udin
10% – 150% of
Udin
Flicker
±5% of reading
0.2 – 10 Pst
Supply Voltage Dips and Swells
Magnitude: ±0.2% of
Udin
Duration: ±1 cycle
N/A
Voltage Interruptions
Duration: ±1 cycle
N/A
Unbalance
±0.15%
0.5% – 5% u2
0.5% – 5% u0
Harmonics
IEC 61000-4-7 Class I
10% – 200% of
Class 3 of
IEC 61000-2-4
Interharmonics
IEC 61000-4-7 Class I
10% – 200% of
Class 3 of
IEC 61000-2-4
Transient Voltage detection
Measurement type
1024 samples/cycle wave shape sampling,
no peak detect
Full scale
8000 V pk
Sample resolution
19.5uSec (50Hz) 16uSec (60Hz).
Interfaces
Color display
Touch screen “Mobile Analysis Lab” with
complete tablet PC functionality
Optional B/W display
PoE self powered G4100 display
Integrated WEB server
Full control and real time monitoring
Integrated FTP server
A standard interface for a main storage
memory
Integrated Telnet server
Command line control and troubleshooting
Communication
Ethernet Ports
3 x 10/100Mb Fast Ethernet Ports,
Integrated router, NAT and Firewall
Power Over Ethernet (PoE)
Available as output,31Watt
Wi-Fi interface
802.11 b/g with integrated antenna
Serial Interface
1 x RS-232, 1 x RS-485
Digital I/O
4 x 5-24VDC digital inputs
Relay
1 x 150V, 10A
Extension slot
1xPCMCIA
Supported Protocols
HTTP, FTP, TELNET, OPC DA, Modbus
RTU,
Wireless Security
WEP, WPA(TKIP), WPA2(AES),
WPA2(Mixed)