User manual

Chapter Four Configuration
Man_805U Rev 1.9 Page 45
Note that these switch settings do not set the system or group addressing - this still needs to
be set by Hayes Commands or the configuration
program.
The four switches are located on the top end-plate,
as per this diagram. If you look at the end of the
module with the front of the module up, then
Switch 1 is the left-most switch, and “on” or 1 is
when the switch is down. The switches in the
diagram have the pattern 0100.
Switch Function Equivalent Hayes Command at
start-up.
Baud rates
0000 Normal Operation – no
change
0100 Restore Factory Defaults. AT&F
1100 Perform Transmit BER Test AT&T0 (for use with AT&T1
at other module - see section
6.2.1)
Serial Radio
0010 Transparent Mode. AT&M0B0C4&L1 9600 19200
1010 AT&M0B1C6&L1 19200 38400
0110 AT&M0B1C9&L1 38400 38400
1110 AT&M0B2C10&L1 57600 76800
0001 Controlled Mode Auto-
connect master.
AT&M2&U1B0C4&E1&Z0=2
&L2
9600 19200
1001 AT&M2&U1B1C6&E1&Z0=2
&L2
19200 38400
0101 AT&M2&U1B1C9&E1&Z0=2
&L2
38400 38400
1101 AT&M2&U1B2C10&E1&Z0=
2&L2
57600 76800
0011 Controlled Mode Auto-
connect slave.
AT&M2&U2B0C4&E1&L3 9600 19200
1011 AT&M2&U2B1C6&E1&L3 19200 38400
0111 AT&M2&U2B1C9&E1&L3 38400 38400
1111 AT&M2&U2B2C10&E1&L3 57600 76800