Chapter Four Configuration
Man_805U Rev 1.9 Page 43
Set the serial data rate to 9600 ATC4
Set the radio data rate to 19200 not necessary (default)
Set the character type to 7,1,2,even AT&B13
Set the operating mode to Transparent Repeater AT&M1&L1
Exit and save the configuration AT&W ATO
Right-hand Unit Configuration
Set the system address to the same random number: AT&S138
Set the group address AT&G2
Set the serial data rate to 9600 ATC4
Set the radio data rate to 19200 not necessary (default)
Set the character type to 7,1,2,even AT&B13
Exit and save the configuration AT&W ATO
Controlled Mode
Auto-connect link with repeaters
Assume that default settings are used for data rates and character types. The only
configuration required is addressing.
Module #1
Set the module to factory default settings: AT&F
Set the system address to a random number: AT&S217
Set the unit address to 1 AT&U1
Set the autodial address to 3 via 2, 100 AT&Z0=2,100,3
Set the operating mode to controlled mode, auto-connect, master AT&M2&L2
Exit and save the configuration AT&W ATO
Note that module #1 is the “master” unit in this link.
Source Repeater Repeater Destination
#1 ----------------> #2 -----------------> #100 --------------------> #3
#101
Apart from being a repeater in the 1 - 3 link, 100 is also in a separate link to 101