4.6 Configuration Examples
Transparent Mode
Extending a PLC Network
Left-hand Unit Configuration
Set the module to factory default settings: AT&F
Set the system address to a random number: AT&S138
Set the group address AT&G1
The group address for the left hand side modules has been set to 1.
Set the serial data rate to 38400 ATC6
Set the radio data rate to 19200 not necessary (default)
Set the character type to 7,1,2,even AT&B13
Exit and save the configuration AT&W ATO
The operating mode will already be in transparent mode from the factory default settings.
The other default values for the other parameters will likely be OK.
Repeater Configuration
Set the module to factory default settings: AT&F
Set the system address to the same random number: AT&S138
Set the group address and unit (secondary group) address AT&G1 AT&U2
The group address for the right hand side module will be set to 2 (this corresponds to the
secondary address of the repeater).
Note that the repeater will only output data to its PLC for messages received from the first 805U. It
will not output data from the right-hand PLC. If you set both group addresses to 1, then the repeater
will output data from both sides - this is only possible when there is only one repeater. The
disadvantage of this is that both sides will hear the re-transmitted message - that is, the PLC that
sent the message will receive the same message back as a re-transmitted message. This is not a
problem with most PLC’s, but is with a small number of brands. For these brands, use a different
group address either side of the repeater.
PLC
PLC
RS485
38.4KB
805U
805U
19.2KB
19.2KB
805U
PLC
RS485
9.6KB
REPEATER
DATA = 7 DATA BITS, 1 START, 2 STOP, EVEN PARITY
PLC
RS485
9.6KB