User's Manual

905U-D Radio Modem Module User Manual
Page 36 © May 2000
Module #100
Note that #100 is the master unit for a link between #100 and #101, It is also acting as
repeater in the #1 to #3 link. The system address for #100 and #101 must be the same as
the other modules so that #100 can act as a repeater.
Set the module to factory default settings: AT&F
Set the system address to the same random number: ATS6 = 17 ATS7 = 50
Set the unit address to 100 ATS8 = 100
Set the operating mode to controlled mode ATS0 = 7
Set the autodial address to 101 AT&Z101
Exit and save the configuration AT&W ATO
The configuration for #101 is not shown as it is not part of the active link.