User manual

915U-2 Wireless I/O Page 93
Page 93 User Manual
38032
Significand at Even / Higher Addressed location. Lower 16 bits of
Significand at lower / Odd addressed location)
(12.3 => 38001=CCCD, 38002=4144)
38033 - 38040
Spare space for floating point values
32501
40000
Not Available
6.1.4 “Holding Registers”
40001
40002
Local AO1 AO2
40003
40020
Spare
40021
40040
Locally attached 115S modules
(See 115S detail below)
40041
40500
(space for up to 24 115S modules)
40501
42500
General Purpose word Storage Used for:
Staging area for data concentrator
Fieldbus Mappings storage
42501
46000
Not Available
46001
46008
Local Pulsed Outputs 1-4. Big Endian Format.
Most significant word at lower / odd address.
46009
46040
Spare 32 bit registers
46041
48000
Not Available
48001
48004
Local Analog outputs as floating point values
Modscan Format (Sign + Exponent + Most significant 7 bits of
significand at Even / Higher Addressed location. Lower 16 bits of
significand at lower / Odd addressed location)
(12.3 => 48001=0xCCCD, 48002=0x4144)