User manual
Page 92 915U-2 Wireless I/O
Page 92 User Manual
12501
30000
Not Available
6.1.3 “Input Registers”
30001
30004
Local AI1 – AI4. (Current Mode)
( AI1, AI2 4-20mA differential, AI3, AI4 4-20mA Sink)
30005
30006
30007
30008
Local Supply voltage (8-40V scaling)
Local Battery voltage
Local 24V loop voltage
115S Supply Voltage
30009
30012
Local AI1 – AI4. (Voltage Mode)
( AI1, AI2 0-10V, AI3, AI4 0-5V)
30013
30016
Local Pulse rate inputs PI1 – PI4
30018
30020
Spare
30021
30040
Locally attached 115smodules
(See 115S detail below)
30041
30500
(space for up to 24 115S modules)
30501
32500
General Purpose word Storage – Used for:
Staging area for data concentrator
Fieldbus Mappings storage
32501
36000
Not Available
36001
36008
Local Pulsed inputs 1-4.Big Endian Format.
Most significant word at lower / odd address.
36009
36040
spare
36041
38000
Not Available
38001
Local Analog inputs as floating point values
Modscan Format (Sign + Exponent + Most significant 7 bits of