Appendix B: I/O Store Registers
6.1.1 “Output Coils”
0001
0008
Local DIO1 – DIO8 (as Outputs) at address 1-8.
0009
0020
Spare
0021
0040
Locally attached 115S modules DIO Outputs
(See 115S detail below)
0041
0500
(space for up to 24 115S modules – 20 registers for each module)
0501
3000
General Purpose Bit Storage – Used for:
Staging area for data concentrator
Fieldbus Mappings storage
Force Mapping registers (assigned in Config)
3001
10000
Not Available
6.1.2 “Input Bits”
10001
10008
Local DIO1 – DIO8 (as inputs) at address 1-8.
10009
10020
Setpoint status from Analog inputs 1 through 12.
10021
10040
Locally attached 115S modules DIO Inputs
(See 115S detail below)
10041
10500
(space for up to 24 115S modules)
10501
10595
WIBMesh - General Purpose Bit Storage: Staging area for data
concentrator Fieldbus Mappings storage
WIBNet - Remote Comms Fail Indication – corresponds to unit
address, e.g. Remote Address 1 - 95
10596
12500
Continuation of General Purpose Bit Storage: Staging area for data
concentrator Fieldbus Mappings storage