User manual

915U-2 Wireless I/O Page 51
Page 51 User Manual
The following table shows the basic onboard I/O available in a standard 915U-2 module
with no expansion I/O connected. For a more detailed I/O map (showing the full register
range), see Appendix B: I/O Store Registers at the end of the manual.
4.2.4 Standard 915U-2 I/O (Basic I/O)
Address
Input / Output Description
0001 - 0008
Local DIO1 DIO8 (as Outputs)
10001 - 10008
Local DIO1 DIO8 (as inputs)
10009 - 10020
Setpoint status from Analog inputs 1 through 12. (AI1, 2, 3, 4
Current Mode), (Internal Supplies), (AI1, 2, 3, 4 Voltage Mode)
30001 - 30004
Local AI1 AI4. (Current Mode)
( AI1, AI2 4-20mA diff, AI3, AI4 4-20mA Sink)
30005
30006
30007
30008
Local Supply voltage (8-40V default scaling)
Local 24V loop voltage (8-40V default scaling)
Local Battery voltage (8-40V default scaling)
115S Expansion I/O Supply Voltage (8-40V default scaling)
30009 - 30012
Local AI1 AI4. (Voltage Mode) ( AI1, AI2 0-25V, AI3, AI4 0-5V)
30013 - 30016
Local Pulse rate inputs PI1 PI4
36001 - 36008
Local Pulsed input counts (PI1 Most significant word is 36001 and
Least significant word is 36002)
38001 - 38032
Local Analog inputs as Floating point values (mA, Volts or Hz)
40001 - 40002
Local AO1 AO2
48001 - 48002
Local AO1 AO2 as floating point values (mA)
4.2.5 I/O Configuration
I/O configuration is done using the Configuration software and each I/O has different
characteristics that can be tailored to applications.
The parameters for each I/O I will explain below.
Digital Inputs
Name The inputs can be named to help with configuration or use the default, up to 30
characters including spaces.
Debounce Time (sec) Debounce is the time which an input must stay stable before
the module decides that a change of state has occurred. If a digital input changes (on -
off) and changes again (off - on) in less than the debounce time, then the module will
ignore both changes. Default debounce time is 0.5 seconds.