The supply voltage also has user-configurable setpoints to determine the Supply Low Volts
alarm. These setpoints can be set from the SetPoint option. The 905K module will shut-down
when the supply voltage reaches 90% of the “low volts” value. We recommend the following
setpoint values:
Battery Type Low Volts Setpoint Shut-down Voltage
BU-5 Battery Pack 6.0 5.4
12V “Gell-cell” 11.2 10.0