User manual
905K Radio Telemetry Module User Manual
ELPRO Technologies Pty Ltd 2010 Page 38
Consider the above
example, with 905K #14.
This module is mounted on
a water tank, and the
analog input is a level
transducer. The 905K is
powered by a BU-5 battery
pack and to conserve
power, a measurement is
taken every 30 minutes
(1800 sec). The transducer
requires a warm-up time of
7 seconds to achieve
accuracy, so a value of 10 seconds is chosen.
In another application involving the continuous monitoring of pressure in a pipeline, values of
zero are chosen for the sample time and warm-up time. The analog loop will be continuously
active and a measurement is taken every 0.5 sec. Because occasional pressure fluctuations
caused a lot of transmissions, then the sample time value was increased to 5 seconds, and a
measurement was taken every 5 sec. Because the warm-up time is still zero, the analog loop is
continuously active.
4.5 Analog Setpoints
A high setpoint value and a
low setpoint value may be
entered. The internal setpoint
status is determined by these
values in comparison to the
analog input value. If the
analog input is less than the
low setpoint, then the setpoint
status is "on". If the analog
input is more than the high
setpoint, then the setpoint
status is "off". When the input
is between the low and high
setpoints, then the setpoint status remains unchanged.
The setpoint values may be set between 0 and 100% of the calibrated range. The low setpoint
may be set to the same value as the high setpoint, however the low setpoint should not be set to a
higher value than the high setpoint.
4.6 Supply Voltage
The supply voltage may be mapped as an internal analog input. The 16 bit value corresponds to
0-30V. There is no analog sensitivity for this measurement - it is only transmitted based on the
configured update time. The measurement is taken every time the 905K transmitter operates.