User manual
Chapter 6 Diagnostics
MAN_905G_1.16 Page 144
6.4.2 Profibus Slave Indicating LED’s
LED No Indication Description
1 - Not Used
2 Green Module is On-Line and data exchange is possible.
2 Off Module is not On-Line
3 Red Module is Off-Line and no data exchange is possible.
3 Off Module is not Off-Line
4 Flashing Red 1
Hz
Error in configuration: IN and/or OUT length set during
initialization of the module is not equal to the length set during
configuration of the network.
4 Flashing Red 2
Hz
Error in User Parameter data: The length/contents of the User
Parameter data set during initialization of the module is not equal
to the length/contents set during configuration of the network.
4 Flashing Red 4
Hz
Error in initialization of the Profibus communication ASIC.
4 Off No diagnostics present
LED n