User manual

Chapter 4 Configuration
MAN_905G_1.16 Page 110
Range 0 -7
Alarm Type
Identifies the alarm type, such as Process Alarm, Plug Alarm etc.
Range 1 -6, 32 -126
Extended Diagnostic Flag
FFh: Slave sends an alarm message with “Extended Diag flag ”set
00h: Slave sends an alarm message with “Extended Diag flag ”cleared
Fault Information
If ‘Invalid Other ’is returned in the Message Information word in the header of the
response, information about the fault can be found here.
000Ah: Failed to execute MSAC1_Alarm_Ack request
000Bh: Remote station failure
0010h: Remote Station DPV1 Failure (see ‘Error Decode’ below).
Error Decode, Error Code 1 & Error Code 2
If ‘Fault Information’ contains error code 0010h, more information according to the
DPV1 specification can be found here.