User manual
Chapter Six Troubleshooting
man_905-105_2.9 Page 53
Chapter Six TROUBLESHOOTING
6.1 Diagnostics Chart
INDICATOR CONDITION MEANING
OK LED OFF Continuously
• Battery Voltage low
• CPU failure
• +24V supply failure/overload
OK LED ON Continuously
• Normal Operation
PWR LED ON Continuously
• Supply available from SUP1/SUP2
• Supply available from solar panel
TX LED ON Flashes briefly
• Radio transmitting
RX LED ON Flashes briefly
• Radio Receiving
• Serial port communicating
RX LED ON Flashes
continuously
• Module in Configuration Mode
RX LED ON Continuously
• Test Button press in Configuration
Mode
No transmission on change of
state
• Unit not configured correctly - re-
configure and check operation
The green OK LED on the front panel indicates correct operation of the unit. This LED extinguishes on
failure as described above. When the OK LED extinguishes shutdown state is indicated. In this state, all
digital outputs turn OFF and the +24V supply turns off.
On processor failure, or on failure during start-up diagnostics, the unit shuts down, and remains in
shutdown until the fault is rectified. The unit also shuts down if the battery voltage falls below 10.8 volts.
This is a protection feature designed to protect the battery from deep discharge in case of extended period
without supply voltage.
6.2 Self Test Functions
6.2.1 Input to Output Reflection (905U-1/105S-1 only)
The unit will require re-configuration after SELF TEST. Ensure you know the required
operational configuration including system and unit addresses so that the network can be
restored after testing.