User manual
Chapter Five Specifications
man_905-105_2.9 Page 37
4.3 Configuration Software
This chapter describes installation and operation of configuration software for the radio and serial
telemetry modules.
The configuration software runs on a conventional PC as a Windows application. The software creates
a configuration file which can be loaded into a module via RS232. The configuration software also
allows the configuration of a module to be loaded for display and modification. Configuration files are
created and stored in project directories.
Configuration of modules consists of entering I/O mappings, and selecting User Options. An I/O
mapping is a link between an input on the module being configured and an output on another module.
A mapping has the form :-
DI3 → Out2 at 4 via 3, 11
This mapping links DI3 on this module to output channel 2 on the module with address 4, and modules
3 and 11 are repeaters.
User Options may be selected to change the configuration of specific features.
Mappings configured to a 905U-C have the form :-
AI2 → I/O Reg 1036 at 10 via 7
This mapping links AI2 on a 905U module to I/O Register 1036 in a 905U-C with address 10. Module
#7 is used as a repeater. The host device connected to the 905U-C can read the I/O register.
4.3.1 Hardware and Software Requirements
The configuration software is available on a CD, and needs to be installed on your PC before you can
use it. The CD contains a setup file called setup.exe. Select the configuration software window on the
Product CD and an installation Wizard will guide you through the installation procedure. To upload
and download configuration files to a module, you will need a RS-232 serial cable as shown below.
105 End PC End
DB9 Male DB9 female
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
Required
Optional