User manual
905U Wireless I/O Module User Manual
105S Serial I/O Module
Page 36 © October 2001
For “-2” and “-3” modules, the default configuration
is as follows :-
Note that there is no default configuration for the “-4” modules.
The following table details the default values for User Options:
Option Factory Set Value
Update transmissions Every 10 minutes
Analog Change-of-state sensitivity 3%
Reset outputs on Comms fail No
Analog Setpoints (if mapped) Low Set point = 30%
High Set point = 75%
Pulse Output Rate Scaling
(if Pulse Rate is mapped)
100 Hz
Digital Input Debounce Time 0.5 seconds
If any of the above values are not appropriate to your system, Section 4.4 below will detail how to change
one or all of the above variables.