User manual
105G Wireless Gateway User Manual
Elpro_man_105g_1.18.doc Page 66
The second example shows another I/O block
(registers 81 to 1080) that has been selected for
scaling only - the sensitivity function has been
disabled (these registers will use the default
sensitivity of 2000 configured on the main
Sensitivity configuration screen).
In this example, the full 16-bit range (0-65535) is
scaled to “signed 16-bit values”. A value greater
than 32767 (which will be seen as a negative value)
can’t be written to the data bus.
In the last example, Scaling has been disabled for
register block 1100 – 1109. Only sensitivity
functionality is being used.
Note: If Scaling is not used at all, up to 50 blocks
can be configured with different sensitivity values.
However if Scaling is used, then only half this
number of blocks is available.
4.6.3 Unit Details
Number of Transmission Retries. - Configurable
value between 0 – 4, If the 105G does not receive an
Acknowledgment from a message it will retry up to
this configured amount.
Note: Setting to 0 will not allow for any retries.
Not recommended for poor radio paths.