Update Times
To change the
update times of
output mappings,
select the Update
Times option. Any
I/O registers that
have already been
mapped to remote
outputs will
automatically be
listed. The default
update time is 10
minutes.
Changing Multiple Settings
You can change the Comms Fail Times or Update Times of several I/O points simultaneously by
using the <Shift> Select feature. For example, if you want to change all times to 1 minute, you
could change each individually, or you could “block” all entries using the “Shift” Select feature
and select “Edit”. You only need to enter the change once to change all of the inputs selected.
This feature is also available with the other configurable parameters.
4.4.3 Don’t Send if in Comm Fail
You can configure a special “Don’t Send if in Comms Fail” mapping. If this is configured for a
particular remote module, the 105G will not transmit output messages to this remote address, if
there is a communications failure status on any input or output configured for the same remote
address. Output messages will re-start when a message is received from the remote module.
The use of this option can prevent the radio channel becoming congested if there are many
outputs at that module.
To configure this
special mapping,
select the “New
Don’t Send in
Comms Fail
Mapping” box. You
will be asked to
select which remote
module this function
applies to. You can
enter more than one
of these mappings if
there is more than
one module.