Chapter 4 Configuration
Page 51 ©February 2009
To map several consecutive I/O registers to several outputs, select the first I/O register in the
range and use “Shift”-select or “Ctrl” - select to highlight the multiple outputs. The selected
mappings will be entered with consecutive I/O registers.
Change Sensitivities
Radio messages to remote modules can be change messages (when the value of the I/O register
changes) or update messages (when the update time has elapsed). If a change message is sent,
the update period restarts.
You can configure the amount of change required to trigger a change message - this is called the
change sensitivity. Sensitivities are configured for blocks of I/O registers - that is, each I/O
register does not have a unique sensitivity. You can configure up to 50 sensitivity values - that
is, there can be 50 blocks of registers with different sensitivities.
For more information on this, refer to section 4.6.