User manual

Chapter 6 Diagnostics
Elpro_man_105g_1.18.doc Page 138
6.2.1 Offline Diagnostics:
The offline diagnostics menu disables the radio protocol driver and the fieldbus protocol driver.
Before displaying the offline debug menu open and start the “terminal” window in configuration
software (see below), or use any third party terminal package.
To display the offline diagnostics menu:
Put the 105G into configuration mode by pressing the small pushbutton switch in the end
plate of the module for 5 seconds (as per section 4.9) until the ACT led flashes - then release
(then the ACT is off and the Serial TX LED flashes once every second);
Type ‘m’ in the terminal window to get the off-line diagnostics menu.
The module will stop normal operations and a menu like the following will appear on the PC
screen for all 105G versions.
Note: Options a), b) and d) are used in factory test and should not be selected.