User manual

105G Wireless Gateway User Manual
Elpro_man_105g_1.18.doc Page 108
Returned data
Return Code
See "Return Codes" in section “DP Error Codes” below.
Fault Information
If ‘Invalid Other ’is returned in the Message Information word in the header of the response,
information about the fault can be found here.
0001h: Address out of range
000Ah: Failed to execute MSAC1_Alarm_Ack request
000Bh: Remote station failure
0010h: Remote Station DPV1 Failure (see ‘Error Decode’ below).
00FFh: Module not initialized
Error Decode, Error Code 1 & Error Code 2
If ‘Fault Information’ contains error code 0010h, more information according to the DPV1
specification can be found here.
DPV1 Acyclic Write
MSAC1_WRITE: Command Number = 0021h
This command initiates a DPV1 Class 1 acyclic write request. Consult EN50170 (DPV1) for
more information.
Command and response layout:
Command
Response
Message ID
(ID) (ID)
Message Information
4002h 0002h
Command Number
0021h 0021h
Data Size
(Size of data) (Size of data)
Extended Word 1
Slave Add Slot No. Slave Add Slot No.
Extended Word 2
Index Length Index Length
Extended Word 3
- -
Extended Word 4
- -
Extended Word 5
- - Error Decode
Extended Word 6
- Err Code1 Err Code2
Extended Word 7
- Return Code
Extended Word 8
- Fault Information
Message data byte 1
Data 1 Data 1
:::
::: :::
Message data byte n
Data n Data n