01h-FFh: Change of address only possible after the initial address (i.e. default address =
126)
Error Code [1 ...4 ]
If ‘Return Code ’ equals 8030h (‘Negative indication from lower layer ’), status values
according to the DP-specification are available in ‘Error Code 1 ’. Error Codes 2 ...3 are
reserved.
(See "Return Codes" and "Error Codes" in section 4.10.5 below.)
Return Code
See "Return Codes" in section 4.10.5 “DP Error Codes”.
Fault Information
If ‘Invalid Other ’is returned in the Message Information word in the header of the response,
information about the fault can be found here.
0001h: Current slave address out of range.
0002h: New slave address out of range.
000Ah: Failed to execute request. (See ‘Return Code’ for additional fault information))
000Bh: Remote station failure. (See ‘Return Code’ for additional fault information)
00FFh: Module not initialized.
Slave Data
With this parameter it is possible to deliver user specific data. The data is stored in the slave
if possible (i.e. EEPROM, FLASH etc.)