Installation Guide Owner manual
Cello Installation Guide
MAN-CELIG (Ver. 1.602)
www.elmomc.com
15
3
Installation
The Cello must be installed in a suitable environment and properly connected to its voltage
supplies and the motor.
3.1 Before You Begin
3.1.1 Site Requirements
You can guarantee the safe operation of the Cello by ensuring that it is installed in an
appropriate environment.
Feature Value
Ambient operating temperature
0 °C to 40 °C (32 °F to 104 °F)
Maximum operating altitude 2,000 m (6562 feet)
Maximum non-condensing humidity 90%
Operating area atmosphere No flammable gases or vapors permitted in area
Models for extended environmental conditions are available.
Caution:
The Cello dissipates its heat by convection. The maximum operating ambient
temperature of 0 °C to 40 °C (32 °F to 104 °F) must not be exceeded.
3.1.2 Hardware Requirements
The components that you will need to install your Cello are:
Component Connector Described in Section Drawing
Main Power Cable VP+ PR 3.4.2.2
Motor Cable M1 M2 M3 3.4.2.1
Backup Supply Cable
(if needed)
24V 3.4.3