Owner manual

610.44520.40.000 4 / 52 © Gardner Denver Deutschland GmbH
Quick start guide
Quick start guide
Side channel blowers are pre-configured for four
operating modes. It only takes a few steps and
they are ready for operation:
ACHTUNG
The drive motor is protected against
overheating by a thermal detector.
If the drive motor gets too hot, the
frequency inverter will switch off the
pump-motor unit.
Please contact the manufacturer if the
hydraulic process does not allow
immediate switch-off.
A minimum wiring is required for
commissioning! ( 22)
1 Read the safety instructions.
The safety instructions start on page 5.
2 Install the pump-motor unit and attach it.
Listing of the mounting steps starts on
page 16.
3 Wire the pump-motor unit.
Please observe that a minimum wiring is
required!
Otherwise commissioning of the pump-
motor unit is not possible.
Important notes concerning the wiring
start on page 22.
4 Put the pump-motor unit into operation.
Description of the commissioning steps
starts on page 34.
5 Adapt important process parameters.
Adapt acceleration and deceleration time to
the hydraulic process via C0012 and
C0013.
Description of parameter changing
starts on page 35.
6 Adjust the speed.
A) Speed adjustment using a potentiometer
The speed is adjusted via the analog input.
The speed can be adjusted between
aminimum and a maximum
value.Description of potentiometer wiring
starts on page 30.
B) Operation with several adjustable fixed
speeds
The speed of the pumpmotor unit can be
adjusted in steps of 1000/min via the digital
inputs E3 and E4.
Description of the wiring of E3 and E4
starts on page30.
C) Operation with one fixed speed
Connect handheld keypad.
Set required fixed speed under C0140.
Disconnect handheld keypad.
The pumpmotor unit will be operated with
this speed when switched on.
Description of handheld keypad
connection and parameter changing
starts on page35.
D) Speed adjustment using the keypad
Connect handheld keypad.
Select C0140.
Set the required speed during the
process using the keys _..
The pumpmotor unit will be operated with
the last set speed when switched on.
Description of handheld keypad
connection and parameter changing
starts on page35.