Owner manual

© Gardner Denver Deutschland GmbH 37 / 52 610.44520.40.000
Commissioning
Changing and saving parameters
All parameters for parameterization or monitoring of the controller are stored in codes. The codes are
numbered and marked with a "C" in the documentation. The available codes are listed in the code
table.
Step Keys Result Action
1. Connect keypad

XX.XX Hz
The function is active.
C0140 = setpoint is indicated via keypad.
2.
 
Select mode ".
3.

XXXX
Select code..
4.
 
Modus off Ahlen.
5.

xxxxx
Parameter onstellen.

Store
Confirm entry when ! is blinking. 6.

Confirm entry when ! is not blinking; is inactive.
7.
Set parameters
Start "loop" again at 2. for further parameter setting.
Changed parameters are stored in the nonvolatile memory of the controller.
5.2.2 Code table
How to read the Code table
Column Abbreviation Meaning
Cxxxx Code number Cxxxx The parameter value is accepted
immediately (ONLINE)

Changed parameter of the code will be accepted after pressing
Code

Changed parameter of the code will be accepted after pressing if
the controller is inhibited
Designation Name of the code
Manufacturer Default setting (value at delivery or after restoring default setting via
C0002)
Further information can be obtained from "IMPORTANT"
Selection 1 {%} 99 Min. value {unit} max. value
IMPORTANT - Brief, important explanations
Code Possible settings IMPORTANT
No. Designation Manu-
facturer
Selection
C0140 Setpoint offset via
keypad
0,00 -650,00 {0,02 Hz} 650,00 Acts additively on
main setpoint.
setpoint 2.
fixed speeds (JOG).
The set value is stored in case of
mains switching or keypad
removal.
C0050 Output frequency -650,00 {Hz} 650,00 Display only: Output frequency
without slip compensation
C0052 Motor voltage 0 {V} 1000 Display only
C0054 Apparent motor
current
0,0 {A} 2000,0 Display only