Owner manual

610.44520.40.000 26 / 52 © Gardner Denver Deutschland GmbH
Installation
NOTE
Do not remove the jumper between terminals
BR1 and BR0!
Otherwise troublefree functioning of the
pumpmotor unit cannot be guaranteed.
4.4.4 Connecting frequency inverters
2FC4302-1NE00 ... 2FC4752-1NE00
DANGER!
Electrical danger!
Improper connection of the pumpmotor unit
can result in an electric shock.
Observe the following basic rules:
The leakage current to earth (PE) is > 3.5
mA. The PE connection must meet EN
50178.
Observe national and regional regulations.
CAUTION
Danger of pumpmotor unit damage caused
by improper connection!
Observe the permissible mains voltage. Any
higher mains voltage will destroy the frequency
inverter.
Wiring according to EMC requirements
(installation of a CE-typical drive system)
The pumpmotor units meet the EU Directive on
"Electromagnetic Compatibility" if they are
installed in accordance with the specifications of
the CEtypical drive system. The enduser is
responsible for maintaining the EU Directive in
the overall system.
NOTE
Requirements for troublefree operation:
Always shield control cables.
Provide largesurface contact between
shielding and shield sheet. Ensure good
electrical contact.