© Gardner Denver Deutschland GmbH 23 / 52 610.44520.40.000
Installation
4.4.2 Preparing works
Open frequency inverter
2FC4152-1NE00 ... 2FC4222-1NE00
ne2bhxn222
Fig. 10: Open frequency inverters 2FC41521NE00
and 2FC42221NE00
2FC4302-1NE00 ... 2FC4752-1NE00
1 2
ne2bhxn422
Fig. 11: Open frequency inverters 2FC43021NE00 ...
2FC47521NE00
4.4.3 Connecting frequency inverters
2FC4152-1NE00 and 2FC4222-1NE00
DANGER!
Electrical danger!
Improper connection of the pumpmotor unit
can result in an electric shock.
Observe the following basic rules:
The leakage current to earth (PE) is
>3.5 mA. The PE connection must meet EN
50178.
Observe national and regional regulations.
CAUTION
Danger of pumpmotor unit damage caused
by improper connection!
Observe the permissible mains voltage. Any
higher mains voltage will destroy the frequency
inverter.
Wiring according to EMC requirements
(installation of a CE-typical drive system)
The pumpmotor units meet the EU Directive on
"Electromagnetic Compatibility" if they are
installed in accordance with the specifications of
the CEtypical drive system. The enduser is
responsible for maintaining the EU Directive in
the overall system.
NOTE
Requirements for troublefree operation:
Always shield control cables.
Provide largesurface contact between
shielding and shield sheet. Ensure good
electrical contact.