Owner's manual

© Gardner Denver Deutschland GmbH 19 / 52 610.44521.40.000
Installation
Mounting sequence:
1 Select suitable mounting elements.
2 Position the pumpmotor unit as close to the
wall as possible on a stable supporting plate
with sufficient loadbearing capacity.
The pumpmotor unit must be positioned
with the base towards the wall.
3 Attach the pumpmotor unit to the wall:
Screw the base of the pumpmotor unit to
the wall via the mounting holes.
When doing so, be sure to provide all
mounting holes with screws!
4 Remove the supporting plate.
4.1.4 Final works
After installing the pumpmotor unit, the eye bolt
must be removed or screwed tightly.
4.2 Mounting of the muffler
The pumpmotor units are supplied with mufflers
for inlet and discharge connections as standard.
The mufflers are marked by arrows in the
following drawings.
2BH1400 … 2BH180. (singleimpeller
pumpmotor units)
ne2bhxn004a
Fig. 7: Mounting of the muffler 2BH1400 … 2BH180.
With the following pumpmotor units, the
inletside muffler is included loose for
packagingrelated reasons. It must be mounted
by the operator.
2BH1310 … 2BH1610 (twoimpeller
pumpmotor units with twostage design)
ne2bhxn004b
Fig. 8: Mounting of the muffler 2BH1310 … 2BH1610
WARNING
Danger from rotating impeller:
cutting/cutting off of extremities!
The rotating impeller is accessible with the inlet
and discharge connections open!
With free entry and exit of gases, i.e. with direct
intake out of the atmosphere or direct feeding
into the atmosphere without piping, the
following therefore applies:
Provide the inlet and discharge connections of
the pumpmotor unit either with additional
mufflers or with additional piping of a sufficient
length to prevent access to the impeller!
4.3 Connecting the pump-motor unit to the
system
4.3.1 Important notes
Delivery direction of the gases
The pumped gases are sucked in via the inlet
connection and discharged via the discharge
connection.
The delivery direction of the gases is marked by
arrows on the connections:
The inlet connection with the corresponding
muffler is marked by an arrow pointing into the
pumpmotor unit.
The discharge connection with the
corresponding muffler is marked by an arrow
pointing out of the pumpmotor unit.