© Gardner Denver Deutschland GmbH
55 / 74
05.2014 · 610.00260.40.000
Power parameters
Motor data
33.001 Motor type Unit: Integer
Relationship to
parameter:
33.010
Parameter HB:
S. xy
Transfer
status:
1
min: 1 Intrinsic value
(to be en-
tered!)
max: 2
Def: 1
Selection of the motor type
1 = Asynchronous motor
2 = Synchronous motor
Depending on the motor type selected, the corresponding pa-
rameters are displayed.
The control mode (parameter 34,010) must also be chosen ac-
cordingly.
33.015 R optimisation Unit: %
Relationship to
parameter:
Parameter HB:
S. xy
Transfer
status:
1
min: 0 Intrinsic value
(to be en-
tered!)
max: 200
Def: 100
If necessary, the start-up behaviour can be optimised using this
parameter.
33.031 Motor current Unit: A
Relationship to
parameter:
5.070
Parameter HB:
S. xy
Transfer
status:
1
min: 0 Intrinsic value
(to be en-
tered!)
max: 150
Def: Type-
specific
Hereby, the rated motor current I
M,N
is set for either star or delta
connection.
33.032 Motor power Unit:
W
Relationship to
parameter:
Parameter HB:
S. xy
Transfer
status:
1
min: 0 Intrinsic value
(to be en-
tered!)
max: 55000
Def: Type-
specific
A
power value [W] P
M,N
that is equal to the rated motor power
must be set here.
33.034 Motor speed Unit: rpm
Relationship to
parameter:
34.120
5.075
Parameter HB:
S. xy
Transfer
status:
1
min: 0 Intrinsic value
(to be en-
tered!)
max: 10000
Def: Type-
specific
Here, the rated motor speed n
M,N
from the type plate data of the
motor should be entered.
33.035 Motor frequency Unit: Hz
Relationship to
parameter:
Parameter HB:
S. xy
Transfer
status:
1
min: 40 Intrinsic value
(to be en-
tered!)
max: 100
Def: Type-
specific
The rated motor frequency f
M,N
is set here.
7.4