Manual
7
Parameters
610.00260.40.000 · 05.2014
46 / 74
© Gardner Denver Deutschland GmbH
2.154 MOP retentive Unit: Integer
Relationship to
parameter:
Parameter HB:
S. xy
Transfer
status:
2
min: 0 Intrinsic value
(to be en-
tered!)
max: 1
Def: 0
Determines whether the setpoint of the motor potentiometer is
retained even after power failure.
0 = disabled
1 = enabled
PID process controller
This mode must be selected in parameter 1,100, the setpoint source must be se-
lected in parameter 1,130, see also fixed frequency, Explanation of operating
modes [➙ 36].
3,050 PID P gain Unit:
Relationship to
parameter:
1.100
1.130
Parameter HB:
S. xy
Transfer
status:
2
min: 0 Intrinsic value
(to be en-
tered!)
max: 100
Def: 0.25
Gain factor proportional component of the PID controller.
3,051 PID P gain Unit: s
-1
Relationship to
parameter:
1.100
1.130
Parameter HB:
S. xy
Transfer
status:
2
min: 0 Intrinsic value
(to be en-
tered!)
max: 100
Def: 0.25
Gain factor integral component of the PID controller.
3,052 PID P gain Unit: s
Relationship to
parameter:
1.100
1.130
Parameter HB:
S. xy
Transfer
status:
2
min: 0 Intrinsic value
(to be en-
tered!)
max: 100
Def: 0
Gain factor differential component of the PID controller.
3,060 PID feedbac
k
Unit: integer
Relationship to
parameter:
1,100
1,130
3,061
Parameter HB:
S. xy
Transfer
status:
2
min: 0 Intrinsic value
(to be en-
tered!)
max: 2
Def: 1
Selection of the input source, from which the actual value for the
PID process controller is read.
0 = analogue input 1
1 = analogue input 2
2 = integrated soft PLC
3,061 PID inverse Unit: integer
Relationship to
parameter:
3,060
Parameter HB:
S. xy
Transfer
status:
2
min: 0 Intrinsic value
(to be en-
tered!)
max: 1
Def: 0
The actual value source (parameter 3,060) is inverted.
0 = disabled
1 = enabled
7.3.4