Technical data

60
Input
Výstup
Input
Výstup
DTNVEM 1/CIB 8590681461501
TECHNICAL PARAMETERS
Internal scheme of changeable module connection
DTNVEM 1/CIB is connected with output in direction of protected device
Typical connection of protector DTNVEM 1/CIB
EAN code
n
n
n
n
Data protectors DTNVEM 1/CIB
Surge guard device (SPD) according to ČSN EN 61643-21 (category A2,B2,C2,C3,D1)
designated for protection of system CIB against thunderstroke overvoltage.
Recommended position is by the start of conduction coming from outside into the
building, then on the edge of other LPZ ( according to EN 62305) and near to protected
device. The lenght between protector and protected device can not be more than
10meters.
DTNVEM 1/CIB is constructed form the base and the changeable module, which
contains its own protection. Base is permanently connected and in the case of revision
or demage, there is manipulation only with changeable module. Base is through-transit
also without changeable module (circuit is on).
Protection is designated for permanent current max.0,5A. Already during the projecting
of aplication is neccessary to secure this max. limit.
Input
Output
Damping diode
Limit impendance
Dual gas tube
Input
Output Input
Output
SPD category according to EN 61643-21:
Rated operation voltage:
Max. permanent operation voltage:
Max. permanent current:
Number of protected pairs:
SPD for system CIB (Foxtrot / iNELS):
Impulse current Iimp (10/350):
Max. tube current Imax (8/20):
Rated tube current In (8/20):
Responce time:
Operation temperature range:
Recommended profi le of connec. contafactors:
Mounting type:
P r o t e c t i o n d eg r e e :
A2,B2, C2, C3, D1
U
n
24V DC
U
c
36V DC
I
N
0,5A DC
1
DTNVEM 1 / CIB
I
imp
2.5kA / wire
I
max
10kA / wire
I
n
1kA / wire
U
P
< 75V (A/B, A/PE, B/PE)
A
< 30 ns
2.5 mm
2
(AWG 12)
on DIN rail 35mm/1.4”
IP20