Technical data
+
-
CIB
CIB
46
It used for regulation of room temperature
Preprogrammed temperature from IDM, can be corrected with the push buttons in
the range of+5°C/-5°C or you can enter the desired room temperature
Display with 2 buttons allows you to enter the desired temperature and changing
modes of heating and cooling circuit (see the function)
Built-in thermo sensor measures ambient temperature
The display readability is assured by active backlight
Heating/cooling circuit is assigned to a thermo-regulator with the support of IDM
YES, built-in thermo sensor NTC
0 to +55°C; 0.3°C from range
±5°C or abs. value
2xbuttons
CIB
symbol display
YES
27 V DC/20 mA from CIB BUS
0.5 - 1 mm
2
0 .. +50 °C
IP 20
II.
2
vertical, downward with CIB terminal
into installation box
85.6 x 85.6 x 20 mm
94 x 94 x 20 mm
73 g
Temperature measuring:
Range / accuracy of temp.measuring:
Heating/cooling circuit correction:
Manual ontrol of heating/
cooling circuit:
Installation:
Display:
Backlight:
Supply voltage/rated current:
Terminals:
Operation temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operation position:
Installation:
Dimensions (plast):
Dimensions (kov, sklo, dřevo, žula):
Weight:
DIMENSIONS AND WEIGHT
CONNECTION
OPERATING CONDITIONS
POWER SUPPLY
COMMUNICATION
INPUTS
TECHNICAL PARAMETERS
Example of connection
IDRT3-1 8595188132510
EAN code
Functions:
Buttons
/
^
is used to correct the temperature range of -5°C/+5°C or enter the
desired temperature in ° C (correction shifts the entire range of time program, i.e.
all heating modes)
IDRT31
Digital room thermo-regulator IDRT3-1