Technical data
37
EAN
Ni, Pt
TC, TZ
0(4)-20
mA
0(1)-10
V
ADC3-40M
+
-
CIB
CIB
Analog-digital converter ADC3-40M
ADC3-40M 8595188132596
DIMENSIONS AND WEIGHT
CONNECTION
Number of inputs:
Galv. separation from inner circuits:
Diagnostic:
Common terminal:
Type of converter:
Converter resolution:
Input resistance (for voltage ranges):
Input types/Measuring ranges
(for each input individually optional
by confi guration in user program
IDM):
Installation BUS:
Unit status indication:
Supply voltage/rated current:
Terminal:
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operating position:
Installation:
Design:
Dimensions:
Weight:
4
No
overload by state
word and LED
GND
approximate
14 bits
approx. 200 kΩ
Voltage (U) : 0 ÷ +10 V (U)
0 ÷ +5 V (U)
0 ÷ +2 V (U)
0 ÷ +1 V (U)
0 ÷ +0,5 V (U)
Current (I) : 0 ÷ +20 mA (I)
4 ÷ +20 mA (I)
Measuring resistance (RTD): Ni1000,
Pt1000, Pt100 (RTD), OV1000, TC, TZ
CIB
green LED RUN
27 V DC/50 mA, from CIB BUS
max. 2.5 mm
2
/1.5 mm
2
with sleeve
-20 .. +55°C
-30 .. +70°C
IP 20 device, IP 40 mounting in the switchboard
II.
2
any
into a switchboard rail to DIN EN 60715
3-MODULE
90 x 52 x 65 mm
112 g
Designed for connection of analog sensors, which generate voltage or current signal
and passive resistive sensors.
Contains 4 analog INPUTS with a resolution of 14 bit AD converter.
Contains 4 analog INPUTS with common terminal GND.
INPUTS are confi gured in IDM, individually as voltage (U) or current (I) and two-wired
connection of resistive sensors (RTD).
Red LED on front panel signals level of analog output out of measuring range
(overload or underload - output disconnection).
ADC3-40M in 3-MODULE version is designed for mounting into a switchboard,
on a DIN rail EN60715.
OPERATING CONDITIONS
POWER SUPPLY
COMMUNICATION
ANALOG INPUTS
Example of connection
TECHNICAL PARAMETERS
n
n
n
n
n
n