Technical data
23
SA3-04M
2
25
28
26
3
35
38
36
4
45
48
46
1
15
18
16
+
-
CIB
CIB
AC 230V
L
N
SA3-04M 8595188132381
4 x NC 16 A/AC1
250 V AC1, 24 V DC
4000 VA/AC1, 384 W/DC
30 A/<3s
3.75 kV, SELV by EN 60950
1000 V AC
100 mA
1200 min
-1
6 min
-1
3 x 10
7
0.7 x 10
5
4x yellow LED
CIB
27 V DC/70 mA, from CIB BUS
green LED RUN
max. 2.5 mm
2
/1.5 mm
2
with sleeve
-20 .. +55 °C
-30 .. +70 °C
IP 20 device, IP 40 mounting in the switchboard
operative control device
individual control device
1.B.E
FR-0
class 2
2.5 kV
II.
2
any
switchboard on DIN rail EN 60715
3-MODUL
90 x 52 x 65 mm
161 g
Output:
Switching voltage:
Switching output:
Surge current:
Insulation voltage between
outputs and internal circuits:
Insulation voltage between individual
relay outputs RE1 to RE4:
Min. switched current:
Switching frequency /no load:
Switching frequency/rated load:
Mechanical life:
Electrical life AC1:
Output indication:
Installation BUS:
Supply voltage/rated current:
Status indication unit:
Terminal:
Operation temperature:
Storing temperature:
Protection degree:
Control device purpose:
Control device constuction:
Automatic operation characteristic:
Heat and fi re resistance category:
Anti-stroke category (immunity):
Rated impulse voltage:
Overvoltage category:
Pollution degree:
Operation position:
Installation:
Design:
Dimensions:
Weight:
It serves for switching of various appliances and loads with potentialless contact.
SA3-04M
contains 4 independent relays with changeover potentialless contacts.
Maximum load per contact is
16 A/4000 VA/AC1.
Each of the two output contacts are individually controllable and addressable.
LED‘s on front panel signal status of each output.
Contact status of each relay can be changed separately and manually by control
buttons on a front panel.
SA3 is normally supplied in the option AgSnO
2
contact material, it can be
supplied with contact AgNi by request.
SA3-04M in 3-MODULE version is designed for mounting into a switchboard, on DIN
rail EN60715.
Example of connection:
OUTPUTS
EAN code
Switching actuator, 4-channel SA3-04M
n
n
n
n
n
n
n
n
TECHNICAL PARAMETERS
DIMENSIONS AND WEIGHT
CONNECTION
OPERATING CONDITIONS
COMMUNICATION
POWER SUPPLY