SA3-02M
+
-
CIB
CIB
AC 230V
L
N
SA3-02M 8595188132374
2x switching 16 A/AC1
250 V AC1, 24 V DC
4000 VA/AC1, 384 W/DC
30 A/<3s
3.75 kV, SELV dle EN 60950
1000 V AC
100 mA
1200 min
-1
6 min
-1
3 x 10
7
0.7 x 10
5
2x red LED
CIB
27 V DC/35 mA, from CIB BUS
green LED RUN
max. 2.5 mm
2
/1.5 mm
2
with sleeve
-20 .. +55 °C
-30 .. +70 °C
IP 20 device, IP 40 mounting in the switchboard
operative control device
individual control device
1.B.E
FR-0
class 2
2.5 kV
II.
2
any
switchboard on DIN rail EN 60715
1-MODUL
90 x 18 x 65 mm
82 g
Output:
Switching voltage:
Switching load:
Surge current:
Insulation voltage between
outputs and built-in circuits:
Insulation voltage between
output relays RE1 and RE2:
Minimal switching current:
Switching frequency/no load:
Switching frequency/rated load:
Mechanical lifetime:
Electrical lifetime AC1:
Outputs indication:
Installation BUS:
Supply voltage/rated current:
Status indication unit:
Terminal:
Operation temperature:
Storing temperature:
Protection degree:
Control device purpose:
Control device constuction:
Automatic operation characteristic:
Heat and fi re resistance category:
Anti-stroke category (immunity):
Rated impulse voltage:
Overvoltage category:
Pollution degree:
Operation position:
Installation:
Design:
Dimensions:
Weight:
It serves for switching of various appliances and loads with potentialless contact.
SA3-02M contains 2 independent relays with changeover potentialless contacts.
Maximum load per contact is 16 A/4000 VA/AC1.
Each of the two output contacts are individually controllable and addressable.
LED‘s on front panel signal status of each output.
Contact status of each relay can be changed separately and manually by control
buttons on a front panel.
SA3 is normally supplied in the option AgSnO
2
contact material, it can be
supplied with contact AgNi by request.
SA3-02M in 1-MODULE version is designed for mounting into a switchboard, on DIN
rail EN60715.
OUTPUTS
Example of connection
TECHNICAL PARAMETERS
EAN code
Switching actuator, 2-channel SA3-02M
n
n
n
n
n
n
n
n
DIMENSIONS AND WEIGHT
CONNECTION
OPERATING CONDITIONS
POWER SUPPLY