Technical data
16
+
+
+
-
-
-
-
Power supply PS3-100/iNELS
PS3-100/iNELS: 8595188131568
Stabilized switching power supply, with the total power of 100 W
It is used to supply central units within intelligent electro-installation iNELS
It is used in MaR fi eld (measurement and regulations)
Fixed output voltage DC 27 V and DC 12 V, galvanically isolated from the mains
Power source of 27 V and 12 V to the GND
Electronic short circuit protection, high-capacity and thermal overload, over voltage
UPS functions - backup outputs 24 V and 12 V batteries connected backup
Recharging the batteries from 27 V source
Protection battery backup fuse - protection against short circuit and reverse polarity
battery
Continuously adjustable maximum battery charging current
Indication of operating and fault conditions 6 LED diodes on the front panel of the power
supply
2 STATUS outputs with open collector for reporting operational status of the source
Source supplies power to the priority system iNELS, the remaining power is used for
rechargeable batteries
When the battery is fully discharged, the battery is automatically disconnected from the load
The device consists of several functional blocks.
The basic part is 100 W power supply with 2 output voltage levels. Voltage of 27.6 V is used to supply the system iNELS and to recharge the batteries. Voltage of 12.2 V is for power as intrusion
detectors (PZTS) or EPS. Both voltages are available without interruption during power AC power supply (UPS function) - assuming they are connected backup battery. Other parts of the
source circuits are back up and recharge the batteries, which provide switching mode connection, charging and disconnect the battery. When in the backup mode, the battery is completely
discharged, the circuit is immediately switched off to avoid the deep discharge. It is guarded by a maximum discharge current - in his crossing of the batteries are also disconnected.
Works if the power supply (oscillations) and its output voltage is greater than 26.9 V, the backup battery charged shock, the maximum value is set by trimmer on the panel source. When
charging the yellow LED CHARGE. Source priority iNELS powers the system and the remaining capacity of up to 100 W only recharges the battery. If the output is high stress and tension
source drops below 26.5 V, UPRI OK LED turns off and disconnects the charge (off and yellow LED CHARGE). Upon further increasing the load further decreases the voltage source and the load
current also fl ows from the battery (power supply and battery power to the load together). Note: If the source is disconnected from the network (does not oscillate) and connect the battery
now, remain disconnected the battery and power outputs are energized. The activation must be connected to the power supply voltage. The last part of the unit signaling circuits and status
outputs. STATUS outputs (see technical data) are equipped with current limiting, so they can directly ballasts without external resistors switched signaling components (e.g. LED, optocouplers
or relay coil).
Features LED indication is given in the specifi cations and in the table below are some examples.
operating switching power supply
output voltage of 27V in order
output voltage of 12 V in order
batteries are recharged
operating switching power supply
output voltage of 27V in order
output voltage is 12 V (short circuit, overload)
batteries are recharged
switching power supply operates
output voltage of 27V in order
output voltage of 12 V in order
source is loaded - battery is not charging
UPS mode
output voltage of 27V in order
output voltage of 12 V in order
battery voltage in order
UPS mode
output voltage of 27V in order
output voltage of 12 V in order
Low Battery
85 – 253 V AC
12 V EZS
27 V iNELS
24 V battery
battery 1
12 V
battery 2
12 V
external DC source
+
EAN code
Example of connection
Description of device functions
LED Signalization