Installation manual

M1EZ8 Installation and Programming
Page 43
SR14: T=00 R=00 r
Phone Line Fault
SR15: T=00 R=00 r
Output 2 Trouble
SR13: 00= Up/ r
Download End
Low Battery T (Trouble) will be reported if the battery drops below 11.2 Volts. Low Battery
R (Restore) will be eligible to report once the battery has passed a test at 11.5 Volts or
higher. Range is 00 to FF. Default is 00 (no report).
Memory Error T (Trouble) will be reported if the system memory checksum fails. An
upload or review of the programming is the only way to detect where the error occurred.
To clear the error and send a R (Restore) you must enter and exit the installer
programming mode. Range is 00 to FF. Default is 00 (no report).
Up/Download End will be reported upon completion of a Up/Download session as a
verification that the control was accessed. Range is 00 to FF. Default is 00 (no report).
Phone Line Fault T (Trouble) will be reported if the Voltage and Current is lost on the
telephone line. Phone Line Fault R (Restore) will report upon restoral of the telephone
line. Range is 00 to FF. Default is 00 (no report).
Output 2 T (Trouble) will be reported if an open circuit occurs on Output 2. Output 2 R
(Restore) will be reported upon restoral of the connection. Range is 00 to FF. Default is
00 (no report).
Menu 12 - Sys Report Code Options & Codes (continued)
Sys Rpt Code Options Description of Option
SR11: T=00 R=00 r
Low Battery
SR12: T=00 R=00 r
Memory Error
System RCs CID SIA
AC Fail 301 A T
AC Restore 301 A R
Automatic Test 602 R P
Aux Over Current 312 Y P
Aux Over Current Restore 312 Y Q
Expansion Module Trouble 333 E T
Expansion Module Restore 333 E R
Local Programming Begin 627 L B
Local Programming End 628 L X
System RCs CID SIA
Log 80% Full 623 J L
Low Backup Battery 302 Y T
Low Battery Restore 302 Y R
Memory Error 304 Y F
Remote Programming End 412 R S
Telephone Line Fault 351 L T
Telephone Line Restore 351 L R
Output 2 Trouble 322 Y A
Output 2 Restore 322 Y H
Based on the event, the CID (Contact ID) or SIA Codes for System Reporting Codes will be:
NOTE: On CID reporting the 3 digit code is preceded by a “1” for new events
or a “3” for restore (previous reported) events.